Why does air conditioner delay
When air conditioner clicks on it delays 10 to 30 minutes or more, indoor blower fan does not run but out door fan does. What could be causing this?
この質問は役に立ちましたか?
When air conditioner clicks on it delays 10 to 30 minutes or more, indoor blower fan does not run but out door fan does. What could be causing this?
この質問は役に立ちましたか?
This sounds like the blower motor needs a new capacitor. You do not want the condenser to run without the inside blower motor running. Is an old post but figured I'd weigh in for future readers. You'll need to shut down power to the air handler/furnace, open it up to gain access to blower motor, and, unplugging the two wires going to the capacitor first, check the capacitor to see if it's reading the correct value. Chances are it isn't.